No. | Name | Technical Characteristic |
Generator set part | ||
1 | Model | 250GFL |
2 | Normal (standby) power | 200kw(220KW) |
3 | Rated frequency | 50HZ |
4 | Rated voltage | 400V/230V |
5 | Rated current | 360A |
6 | Rated speed | 1500RPM |
7 | Speed mode | Electronic speed control |
8 | Startup method | 24VDC (25KW) electric motor starter |
9 | Battery charging method | Gas engine drives charging generator |
10 | Air intake method | Low pressure air intake,2-10kPa |
11 | Steady state voltage regulation % | ≤±1.5% |
12 | Voltage fluctuation rate% | ≤1% |
13 | Voltage stabilization time/s | ≤1s |
14 | Instantaneous voltage regulation % | ≤±20% |
15 | Steady state frequency adjustment rate% | ≤1%(Adjustable) |
16 | Transient frequency regulation rate% | -10%~12% |
17 | Frequency volatility% | ≤1% |
18 | Frequency stabilization time/s | ≤10 |
19 | Gas consumption rate (at 100% load) | ≤230g/Nm3 |
20 | Power generation efficiency% | 34% |
21 | Single genset weight/kg | 2350 |
22 | Dimensions of a single genset (with common base, support) | 3000*1300*1700mm |
Engine part | ||
24 | Engine model | SC15GT380D2 |
25 | Engine Brand | Ronghuan |
26 | Engine speed | 1500RPM |
27 | Engine power | 255/280kw |
28 | Number of cylinders | 6 |
29 | Cylinder arrangement | Line Engine |
30 | Cylinder diameter mm | 135 |
31 | Stroke mm | 165 |
32 | Single cylinder displacement/L | 2.36 |
33 | Total displacement/L | 14.2 |
34 | Compression ratio | 9.5:1 |
35 | Gas consumption rate (Gas calorific value ≥ 31.0MJ/Nm3) |
≤ 0.3 |
36 | Lubricating oil consumption rate at rated power | ≤0.3g/kw·h |
37 | Engine weight | 1250kg |
38 | Engine dimensions | 2261*1209*2410 |
39 | Exhaust temperature after turbine | ≤550ºC |
40 | Rotation direction | Counterclockwise rotation when viewed from the flywheel housing |
41 | Spark plug electrode gap | 0.40mm |
42 | Thermal efficiency | 44% |
43 | Ambient temperature | 5-40ºC |
44 | Intercooling temperature | 54ºC |
45 | Maximum oil pan capacity (minimum capacity) | 36L |
Alternator part | ||
46 | Model | HJI200 |
47 | Type | 3-phase, 4-wire, additional winding excitation |
48 | Rated output power | 200KW |
49 | Rated voltage | 380V(AC) |
50 | Frequency | 50HZ |
51 | Efficiency | 94.50% |
52 | Insulation Class | H |
53 | Protection level | IP23 |
54 | Cooling method | Air cooling, self-heating |
55 | Anti-interference standard | N |
56 | AVR (voltage regulator): | R448 |
57 | Phase voltage balance rate | ≤0.5% |
58 | Transient voltage regulation rate | +20%,-15% |
59 | Steady state voltage regulation | ±0.5% |
60 | Short circuit current capability | 300% (3 times), 10s |
Control and parallel system (optional according to needs) | ||
61 | Controller Model | Imported single controller or SMRT controller |
62 | Parallel controller performance characteristics | The digital intelligent controller (which can set the size of the input load) is the main control element of the fully automatic and grid-connected system. The parameters of the unit are summarized and displayed here, and all the results and commands calculated by the program are also sent by the controller to each actuator through the corresponding control output port. The controller adopts microprocessing technology and writes software through algorithms suitable for generator sets to improve the control of the unit's output voltage, voltage phase, active power and reactive power; the controller has a simple operation interface and complete functions. The operating status, communication status, fault status and operating parameter settings of all generator sets can be monitored and adjusted through the buttons on the panel. AVRI interface expansion module is used for parallel or mains connection. The parallel module is a comprehensive parallel controller for single and multiple generator sets. The simple setting allows customers to choose the appropriate application mode. The main functions are as follows: ·Automatic start in case of mains failure, long-term parallel operation ·Can be connected to ECUs with J1939, Modbus and some special protocols for trial, and alarms are displayed in text ·Base load, input/output, peripheral power control ·Configurable input and output ports ·Fault history up to 500 items |
63 | Parallel switch (brand) | Chint air switch: The product has excellent performance and high reliability, providing a complete protection solution for the power distribution system. Air switches can be installed in low-voltage distribution cabinets as main switches, and are used in distribution networks with AC 50Hz, rated working voltages of 400V and 690V, rated insulation voltages of 1000V, and rated working currents of 6300A and below, to distribute electric energy and protect lines and equipment from overload, short circuit, undervoltage, and ground faults. It has a variety of protection modules and communication modules to improve the safety and reliability of power grid operation and meet the needs of power distribution system automation. |
64 | Parallel cabinet characteristics | The parallel cabinets we provide have the following characteristics: reliable design and safe debugging; reliable and complete protection links, safe and beautiful line layout, in full compliance with electrical specifications, complete sound and light fault alarm, with lighting and sound links, simple operation, safe and reliable, using reliable performance components produced by professional manufacturers, reasonable layout, and beautiful appearance |
Others | ||
65 | Genset supporting components | The gas engine and generator are connected with elastic standard and installed on the common base. The coaxiality of the unit after assembly is guaranteed to be ≤0.2mm. The common base is made of high-strength steel. The gas engine and generator base are connected with the common base with shock absorption. |
66 | Standard scope of supply of generator sets | Intake system: air filter/crankcase ventilation line Cooling system: fresh water pump/thermostat/expansion tank, water tank Lubricating oil system: oil pump/paper filter oil filter/oil cooler Gas supply system: stainless steel ball valve, solenoid valve, butterfly valve and needle valve Exhaust system: exhaust pipe/muffler/expansion joint and matching flange Starting system: charging motor DC24V/electric starter motor Speed control system: DC24V electronic speed regulator Ignition system: digital ECU ignition module, Hall sensor, high-voltage ignition coil and high-performance spark plug Generator: AVR automatic voltage regulator |
67 | Technical documents and Parts | 1. Starter battery pack. 2. Primary muffler. 3. Mounting parts, including expansion damping joint, damping pad, battery connection cable, tailpipe elbow, etc. 4. Replaceable filter, including air filter and oil filter. 5. User manual. 6. Genset factory test report 7. Product quality certificate |